当前位置: 首页 > 讨论区 > 讨论区详情
连接本地PI时,出现timeout错误
邓道军| 2020-01-13
1
2125

I 14-Nov-19 12:45:53 pilogsrv                                               (0)

 >> 14-Nov-19 12:45:53  PIChinaNetIso.exe>PI-API> pinetread> select timeout, host 127.0.0.1:5450 not responding

I 14-Nov-19 12:45:53 pilogsrv                                               (0)

 >> 14-Nov-19 12:45:53  PIChinaNetIso.exe>> DataSync:Disconnecting from local PI server

I 14-Nov-19 12:45:55 pilogsrv                                               (0)

 >> 14-Nov-19 12:45:55  PIChinaNetIso.exe>> DataSync:Failed to connect to local PI server. Waiting for connection.

1分钟,连接回复:

I 14-Nov-19 12:46:55 pilogsrv                                               (0)

 >> 14-Nov-19 12:46:55  PIChinaNetIso.exe>PI-API> Successful reconnection to [127.0.0.1:5450](127.0.0.1) Buffered[0]

I 14-Nov-19 12:46:55 pilogsrv                                               (0)

 >> 14-Nov-19 12:46:55  PIChinaNetIso.exe>> DataSync:Successfully connected to default PI server


再断开、再连接,如此不断循环。。


收藏
  • 邓道军|发表于:2020-01-13
    在重启接口、网闸、服务器均无效后,需将PI Data Archive升级至3.4.410.1129(2017)或更高版本。